Machine room Ventilation - INTERNATIONAL CODEJune 18, 2015INPUT1Project Name:My Project NameProgram User:My Name HereRoom Floor Area, Sq. ,200Room Height, Summer 1% DB Temp, F:92ASHRAE Winter 99% Design Temp, F:8Heating Indoor Design Temp, F:50Max Summer Indoor Design Temp, F:10Building code :1Project Insurance Type:1Machine room Construction Type:2Refrigerant Type:1Number of Emergency Exhaust Fans:3Total room Motor Load, HP2,500Compressor Motor Typical for Premium Efficiency MotorsRefrigerant in Largest System, ,000TOTALRGROSSVALUEITEMAREAINSULATIONSQ FTONLYROOF2,20019EXTERIOR WALL - NORTH1,5007EXTERIOR WALL - EAST1,3507EXTERIOR WALL - SOUTH07EXTERIOR WALL - WEST1,3507EXTERIOR DOORS42N/AOUTPUTlWinter Envelope Heating Load.

Machine Room Ventilation - INTERNATIONAL CODE June 18, 2015 OUTPUT l Intake Wall Louver Area, Emergency Ventilation Rate Q 24,200 V 700 Intake Wall Louver Area, Sq Ft = 34.6 x 2 (50% free area louver) = 69.1 Sq Ft