Tr oubleshooting Guide Compressor runs ; No Cooling This situation could be the result of one of three main conditions: 1) System is low on refrigerant (undercharge/leak) or has an excess of refrigerant (overcharge). ) For guidance see our fact sheet Refrigerant R134a Charge Guidelines . 2) Compressor is damaged and unable to achieve sufficient differential pressures. This is highly unlikely and not to be considered at this stage. 3) There is a blockage somewhere in the refrigerant circuit. This is possible. Frigoboat systems employ a capillary tube (cap tube) metering device to separate the high and low pressure sides of the system.
Troubleshooting Guide – Compressor Runs; No Cooling This situation could be the result of one of three main conditions: 1) System is low on refrigerant (undercharge/leak) or has an excess of refrigerant (overcharge).
Download Troubleshooting Guide – Compressor Runs; No …
Information
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
Related search queries
Gyrolok Fitting Locator 2 Gyrolok, Tube, Naso-jejunal tube, Inserted, Information for patients havinga naso-jejunal tube, OPTIMIZING CONDENSER TUBE LIFE WITH, OPTIMIZING CONDENSER TUBE LIFE WITH NONDESTRUCTIVE, Tube Guidelines Post-Operative Instructions, VOSSFormSQR Tube Couplings, When to Change a Tracheostomy Tube