Typical Specifications For Dynaforce® Hydronic …
Typical Specifications ForDynaforce Hydronic heating BoilersModels DR(H) 0300 DR(H) 500099-0129Rev 06The heating boiler shall be a CAMUSDynaforce model _______ having an input rating of __________ Btu (kW) /hr. and__________Btu (kW)/hr output for Hydronic Hydronic heating boiler shall be design certified by CSA International and shall meet the requirements of ANSI , and The heating boiler shall be vented as a Category II or IV condensing Overview:-Boiler shall operate up to99%thermalefficiency-Heat exchangershall bea fully condensingverticalcylindrical counter-flow water tube design with 439gradetubes and 316Lgrade headers ofstainlesssteel constructionand allwelded design with constantallowablesystem returntemperatures tuned combustion premix providing homogeneous air and gascombustionmixtoa radialburner incorporating aknittedstainless steelwrap ensuring stable light off and efficient clean :1gas i
Typical Specifications For Dynaforce® Hydronic Heating Boilers Models DR(H) 0300 – DR(H) 5000 99-0129 Rev 06 Controls: Standard controls include a SOLA electronic proportional integrated combination ignition limit/operator control accurate to 10F (0.50C)