Transcription of 2301A Electronic Load Sharing and Speed Control
{{id}} {{{paragraph}}}
Product Manual 82389 (Revision U, 7/2016) Original Instructions 2301A Electronic load Sharing and Speed Control 9905/9907 Series CSA Certified LR46653 Installation and Operation Manual General Precautions Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. Revisions This publication may have been revised or updated since this copy was produced.
Apr 18, 2019 · Speed Sensor Input Impedance 100–300 Ω Speed Sensor magnetic pickup 1.0 Vac minimum to 30 Vac maximum Speed Trim 0–100 Ω for 0 to 10% speed change Speed Setting terminals 23–24 jumpered, internally adjustable 100 Ω potentiometer allows external 0–10% speed trim Idle Speed Select external switch, open terminals 19 to 16