4007ES Fire Control Panels

Features Flexible standard combination of addressable initiation and addressable notification (109 mm) Diagonal color touchscreen display: Convenient and intuitive user interface provides detailed system status and individual point information Supports dual language selection, including unicode character languages A custom background display appears when operation is normal (see page 7 for details) Includes a 3 A IDNAC SLC (signaling line circuit) output power supply that provides enhanced power delivery to addressable notification appliances: A constant 29 VDC source voltage is maintained during alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, and smaller gauge wiring.

monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches can communicate their identity and status and receive fire alarm system control. Additional addressable interface modules include circuit isolators, conventional IDC