UCL Fire Safety Technical Note - TN001 _____ Date Last Amended: Dec 17 1. Issued by the Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities. Fire Safety Technical Note ACCESS SECURITY SYSTEMS ( electronic LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE ACCESS SECURITY & Accessible Door Opening SYSTEMS - what you need to know: Reference - BS 7273-4: 2015 Code of Practice for the Operation of Fire Protection Measures - Part 4: Actuation of Release Mechanisms for Doors. Mandatory ACCESS and SECURITY controlled locking SYSTEMS on doors or automatic sliding doors that form part of the Means of Escape (MoE) with opening ironmongery that does not have a mechanical override in the direction of escape, but relies on the release of Electro-magnetic lock or keep by a code / push button / reader device shall fail open/unlocked.