Transcription of Anderson Greenwood SerieS 400 PiSton Pilot PoPrV ...
{{id}} {{{paragraph}}}
Anderson Greenwood SerieS 400 PiSton Pilot PoPrVInstallatIon and maintenance InstructIons1 GenerAl vAlve description And Generalthe Anderson Greenwood SerieS 400 valve is designed for modulating action. the main valve will open at nameplate set, but only an amount proportional to the relieving capacity required. As process pressure increases, the valve will open more and be in full lift at 110% of main valve uses the principle of pressurizing the top or large area of a differential area PiSton with line pressure to hold the PiSton closed up to set pressure. At set pressure, the Pilot relieves, depressurizing the volume above the PiSton , the main valve dome, and the PiSton lifts permitting discharge from the main valve. As capacity relief of the system installationeither or both inlet and outlet may be standard AnSi flanges or AnSi pipe threaded connections and are to be installed in accordance with accepted piping remote pressure pick-up is used the Pilot supply tube is connected to a remote location rather than to the inlet neck of the valve.
Anderson Greenwood SerieS 400 PiSton Pilot PoPrV InstallatIon and MaIntenance InstructIons 1 GenerAl vAlve description And stArt-up 1.1 General the Anderson Greenwood Series 400 valve is