November 2011 SYS-APM001-ENApplications Engineering ManualChiller System Design and ControlChiller System Design and ControlSusanna Hanson, Applications engineer Mick Schwedler, Applications manager Beth Bakkum, information designer 2009 Trane All rights reservedChiller System Design and ControlSYS-APM001-ENTrane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the Engineering professional.
condenser-water temperature drops, so do refrigerant temperature and pressure. As the refrigerant pressure and temperature changes, the work a compressor must do also changes. The effect of leaving-condenser-water temperature change on power consumption can be 1.0 to 2.2 percent per degree Fahrenheit [1.8 to 4.0 percent per degree Celsius].