testing guide Why backup batteries are needed Battery types Failure modes Maintenance philosophies Practical Battery testing Frequently asked questions Megger products overviewBattery testing GUIDe3 ContentsWhy backup batteries are needed .. 4 Why test Battery systems .. 4 Why batteries fail .. 4 Battery types .. 5 Lead-acid overview .. 5 Nickel-Cadmium Overview .. 5 Battery construction and nomenclature .. 6 Configurations .. 6 Single post batteries .. 6 Multiple post batteries .. 6 Failure modes .. 7 Lead-acid (flooded) failure modes .. 7 Lead-acid (VrLa) failure modes .. 7 Nickel-Cadmium failure modes .. 8 Maintenance philosophies .. 9 How to maintain the Battery .. 9 Standards and common practices .. 9 Ieee 450 .. 9 Inspections .. 9 Capacity test (discharge test) should be done .. 9 Ieee 1188 .. 10 Inspections .. 10 Capacity test (capacity test) should be done .. 10 Battery replacement criteria .. 10 Ieee 1106 .. 10 Inspections.
In flooded batteries, they escape and water must be periodically added. In valve-regulated, lead-acid (sealed) batteries, the hydrogen and oxygen gases recombine to form water. Additionally, in VRLA batteries, the acid is immo-bilized by an absorbed glass matte (AGM) or in a gel. The matte is much like the fibre-glass insulation used in houses.