APPENDIX C - ELEVATORS. The following outline specifications supplement BSRV ELEVATORS, and are to be incorporated into specifications for new and replacement hydraulic ELEVATOR work contracted by the University of Virginia. GENERAL REQUIREMENTS FOR ALL ELEVATOR INSTALLATIONS. Under no circumstances will manufacturers or suppliers of proprietary equipment, systems, or software, other than those specifically noted in this Appendix, be accepted. The REQUIREMENTS of this appendix shall apply to both new construction projects and to the modernization of existing elevators.
C.1.4 ELEVATOR PIT REQUIREMENTS 1. Provide continuous, non -slip, horizontal rungs every 12” for the full height of the pit ladder. 2. All elevator hoistways must be equipped with a sump pit located at the rear of the elevator pit. Metal grating shall be installed over the hole that sits flush with the pit floor. 3.