CAPACITY CALCULATIONS FOR STEAM LOADS

189 EngineeringSTEAM TRAP SIZING AND SELECTIONDrip Trap on STEAM Mains:Should be sized for 2X safety factor at full differential pressurePrimary choice for trap: 1/2 WD600L Thermodynamic3/4 WD600L ThermodynamicPlace trap every 200 ft. depending on type size, pressure,and piping Tracing:Typically a trap is placed approximately every 100 choice for trap: 1/2 WT2000 Thermostatic1/2 WT1000 ThermostaticBucket traps and thermodynamic traps are used on critical tracing applications where no condensate can Applications.

191 Engineering E N G I N E E R I N G Warm Up Loads in Pounds of Steam per hour per 100 ft. of Steam Main Steam Pressure (psig) 2” 2-1/2” 3” 4” 5” 6” 8” 10” 12 14