Session 12 Ex Protection ConceptsEx Protection ConceptsElectricalElectrical Symbol Typical IEC EPLT ypical Zones IEC Standard Basic concept of protectionIncreased safety e Gb 1,2 IEC 60079 7 No arcs, sparks or hot surfaces. Enclosure IP54 or betterType n (non sparking) nA Gc2 IEC 60079 15 Flameproofd Gb 1,2 IEC 60079 1 Contain the explosion, quench the flameType n (enclosed break) nC Gc2 IEC 60079 15 Quartz/sand filled q Gb 1,2 IEC 60079 5 Quench the flameIntrinsic safety ia Ga 0,1,2 IEC 60079 11 Limit the energy of sparks and surface temperaturesIntrinsic safety ib Gb 1,2 IEC 60079 11 intrinsic safety ic Gc2 IEC 60079 11 Type n (energy limitation)
Intrinsic safety i 21 IEC 60079‐11 Similar to t, but with some relaxations if circuit inside is intrinsically safe Encapsulation m 22 IEC 60079‐18 Protection by encapsulation of incendive parts Pressurised p Db,Dc 21,22 IEC 60079‐2 Protection by pressurisationof enclosure