Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 6. WALL CONSTRUCTION . Design and CONSTRUCTION . Exterior walls of SECTION R601. wood-frame CONSTRUCTION shall be designed and constructed in GENERAL. accordance with the provisions of this CHAPTER and Figures Application. The provisions of this CHAPTER shall con- (1) and (2) or in accordance with AF&PA's trol the design and CONSTRUCTION of all walls and partitions for NDS. Components of exterior walls shall be fastened in accor- all buildings.
40 percent and up to 60 percent shall also be doubled with no more than two successive doubled studs bored. See Figures R602.6(1) and R602.6(2). Exception: Use of approved stud shoes is permitted when they are installed in accordance with the manu-facturer’s recommendations. R602.6.1 Drillingandnotchingoftopplate.Whenpiping