11 .. Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 7A [SFM] MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE > > > SECTION 701A SCOPE, PURPOSE AND APPLICATION Scope. This CHAPTER applies to building MATERIALS , sys-tems and/or assemblies used in the exterior design and con-struction of new buildings located within a Wildland-Urban Interface Fire Area as defined in Section 702A. Purpose. The purpose of this CHAPTER is to establish minimum standards for the protection of life and property by increasing the ability of a building located in any Fire Hazard Severity Zone within State Responsibility Areas or any Wildland-Urban Interface Fire Area to resist the intrusion of flames or burning embers projected by a vegetation fire and contributes to a systematic reduction in conflagration losses. Application. New buildings located in any Fire Hazard Severity Zone or any Wildland-Urban Interface Fire Area des-ignated by the enforcing agency constructed after the applica-tion date shall comply with the provisions of this CHAPTER .
Group U occupancy and not exceeding 120 square feet in floor area, when located at least 30 feet from an applicable building. 2. Buildings of an accessory character classified as Group U occupancy of any size located least 50 feet from an applicable building. 3. Buildings classified as a Group U Agricultural Build-