Chilled-Water System Decisions

Providing insights for today's hvac System designer Engineers Newsletter volume 47 3. impacts of Chilled-Water System Design Decisions Primary-secondary System bypass This Engineers Newsletter walks through a number of design Decisions , with Bypass line sizing sizing. The premise of a primary- discussion and examples to explain how secondary System is to hydraulically This seemingly simple decision can have and why those Decisions are made. separate (decouple) the primary ( chiller ). significant consequences if not done flow from the secondary ( System ) flow.

series chillers and power consumption † whether to use pressure-independent control valves Primary-secondary system bypass sizing. The premise of a primary-secondary system is to hydraulically separate (decouple) the primary (chiller) flow from the secondary (system) flow. This decoupling prevents the operating