Transcription of CODE OF PRACTICE 101 FOR DISTRIBUTION SUBSTATION …
{{id}} {{{paragraph}}}
Information Class: PROPRIETARY CODE OF PRACTICE 101 FOR DISTRIBUTION SUBSTATION DESIGN Version 15 Issued By : Asset Management Department Asset Development Branch Date of Issue : 30 June, 2020 Code of PRACTICE No. 101 for DISTRIBUTION SUBSTATION Design Version 15 June 2020 Content - 1 Information Class: PROPRIETARY CODE OF PRACTICE 101 FOR DISTRIBUTION SUBSTATION DESIGN VERSION 15 CONTENTS Page 1. INTRODUCTION 1 2. OBJECTIVES 1 3. PROJECT MANAGEMENT 1 4. ELECTRICAL EQUIPMENT IN DISTRIBUTION SUBSTATION 2 5. ARCHITECTURAL/CIVIL DESIGN 6 6. VENTILATION DESIGN 23 7. LIGHTING DESIGN 25 8. ELECTRICAL SERVICES DESIGN 26 9. FIRE SERVICES DESIGN 28 10. CUSTOMER MAIN SWITCHROOM DESIGN 32 11. OUTDOOR SUBSTATION 36 12.
switchboard. Distribution transformer - 900mm around the LV terminals. - 750mm on the other sides. LV board - 1000mm in front of the board. - 750mm on the sides where cables turn in and out. - The cable trench edge shall be 120mm from wall. - Two wall mounted eye bolts with safety loading of 1 ton shall be provided at 2.7m