December 17, 2015 Comment Response Letter Re: Project Number 12- 2015 The purpose of this Letter is to address comments received from you via e-mail on 2015 -10-27-17 regarding the aforementioned project. For your convenience and to expedite the review and approval process, your original comments are included and Benjamin-Ryan responses are provided in BOLD. FIRE REVIEW 1. The project has failed fire review. An additional fire hydrant is required. See red line plans page Response : Additional proposed new fire hydrants provided to meet fire flow and maximum distance of 300-feet. 2. This project shall comply with the Milton Municipal Code, the 2012 International Fire Code and the set standards of Milton as established by the Fire Chief. (NFPA) Response : 2012 IFC has been considered for this Project. 3. The site or building address shall be displayed at the start of construction, either visible from or at the nearest access street.
December 17 , 2015 . Comment Response Letter . Re: Project Number 12-2015. The purpose of this letter is to address comments received from you via e-mail on 2015 …