COMMERCIAL ELECTRICAL INSPECTION CHECKLISTS (2008 …

1 COMMERCIAL ELECTRICAL INSPECTION CHECKLISTS ( 2008 NEC) ROUGH UNDERGROUND INSPECTIONS CHECKLISTS Rough Underground Inspections - Key Questions 1. What type of occupancy? 2. What types of wiring methods are being used? 3. Are the wiring methods suitable for the location? 4. Is the conduit fill expected to be within the maximum allowable by Table 1, Chapter 9? 5. Does the number of bends in conduit exceed 360 degrees? 6. Is the wiring method listed and are listed fittings used? 7. Does the installation match that shown on the blueprints? 8. Are there any special grounding and bonding requirements (such as for patient care locations)? 9. Is the workmanship suitable and are the fittings made up tight? 10. Is corrosion protection a concern for the wiring method used? 11. Is a concrete-encased electrode present? 12. Are suitable floor boxes, under-floor raceways installed properly?

1 COMMERCIAL ELECTRICAL INSPECTION CHECKLISTS (2008 NEC) ROUGH UNDERGROUND INSPECTIONS CHECKLISTS Rough Underground Inspections - Key Questions