Communication Facilities Construction Design Standards

DukeOIT Office of Information Technology ~ e B1cs1 RCDD _____ Communication Facilities Construction Design Standards February 2016 Rev. 8/2/16 2 Contents 1 Introduction ..3 Planning and Design ..3 Responsibilities ..3 2 Building Communications Service Entrance ..4 Routing of underground Building feed cables ..4 3 Main Distribution Frame Room (MDF)..4 Size ..5 Electrical Structure requirements ..7 4 Intermediate Distribution Frame Room (IDF) ..8 Size ..8 Other 5 Intra-building Distribution System ..8 Horizontal cabling system.

Construction drawings shall provide a minimum of four 4" conduits extending from a manhole (typically located 5' 0" outside the building) and terminating in the ... Where the entrance conduits penetrate the foundation, footings, or outside walls of a building, rigid metallic conduit shall be used. Plaster fiber ducts or aluminum conduit are not ...