Distribution System Phase Attribute …

Distribution System Phase Attribute Measurements Using The Origo PhaseID System1 Origo Corporation 2004 Technology Made Simple Distribution System Phase Attribute Measurements Using the Origo PhaseID System Introduction The Origo PhaseID System measures Phase in a power Distribution System by using a GPS timing signal to simultaneously measure voltage Phase at a base and field location. By comparing the unknown Phase at the field location to the known Phase at the base location, the unknown field Phase Attribute can be deter-mined. This white paper explains how we would expect voltage Phase to vary at different points in the Distribution System , as it passes though various transmission and Distribution transformers and power lines. Potential sources of Phase measurement error, and their magnitude, are discussed. Phase Shift Through Ideal Transformers Delta-Grounded Wye A popular substation transformer connection is the delta-grounded wye illustrated in figure 1.

© Origo Corporation 2004 4 Technology Made Simple Ungrounded Wye-Delta The ungrounded wye-delta connection is typically used to provide service to a combination ...