EI 1581 5th EditionCOMPLETE AVIATION FILTRATION SYSTEMST hree categories, defined by fuel being used Category C filter/separators are for use in commercial Jet-A or Jet-A1 fuel. They are tested in fuel containing Stadis 450 and DCI-4A. Category M filter/separators are for use in military JP-8 or JP-5 fuel. They are tested in fuel containing Stadis 450, DCI-4A and Di-EGME (FSII). Note: testing to Category M also qualifies for Category C Category M100 filter/separators are for use in military JP-8+100 fuel. They are tested in fuel containing Stadis 450, DCI-4A, Di-EGME (FSII) and Spec Aid 8Q462. Note: testing to Category M100 does not qualifiy for Category M Two type of vessels, depending on location used Type S filter/separators are used at filtration points where significant levels of both dirt and water can be expected.
EI 1581 5th Edition COMPLETE AVIATION FILTRATION SYSTEMS Three categories, defined by fuel being used • Category “C” filter/separators are for use in commercial Jet-A or Jet-A1 fuel.