Elastimold Cable 600 Series Cam-Op , and Link-Op deadbreakconnector systems incorporate provisions for hotstick operation ofDE-ENERGIZED primary feeder or network circuits. Configurations allowexternal visible break, testing, grounding and isolation. Retrofit kits allowupgrading existing systems utilize pin and socket connectors. Link-Op connectorsare bolted and installed using torque controlled tools. Either system canbe retrofitted to existing Cam-Op and Link-Op connectors are unique, allowing all hotstickoperations to be completed without moving the cable, an importantconsideration when large, stiff cables prohibit Cam-Op connector is easily installed or removed by hotstickoperation of the cam action disconnect page A3 A4 for complete Ratings600 and 900 A Continuous25 kA sym., 10 cyclesNOTE: 900 A ratings require copper cable and copper current-carrying Ratings15 kV kV kV Phase-to-Phase95 kV BIL34 kV AC Withstand53 kV DC Withstand11 kV Corona Extinction25 kV kV kV Phase-to-Phase125 kV BIL40 kV AC Withstand78 kV DC Withstand19 kV Corona Extinction35 kV kV kV Phase-to-Phase150 kV BIL50 kV AC Withstand103 kV DC Withstand26 kV Corona ExtinctionCAM-OP and LINK-OP SYSTEM 600 SERIES DEADBREAKRETROFIT COMPONENTS FOREXISTING EQUIPMENT W/OPROVISIONS FOR MOUNTABLEINSULATED BUSHINGCABLE TO EQUIPMENTEQUIPMENTBUSHINGS
Elastimold ® Cable Accessories www.tnb.ca A17 Illustration (not to scale) Description Voltage Class E LASTIMO D Cat .No Notes CAM-OP CONNECTOR KIT 15 kV 25 kV 35 kV 655LINK-C-LR-W0X-B-DRG