PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: stock market

FIRE DAMPER INSTALLATION, OPERATION & MAINTENANCE ...

R8218 NCA MANUFACTURING INC. 1985 CARROLL ST. CLEARWATER, FL 33765 DAMPER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONSIOM - fire DAMPERS - 0718 The following installation instructions are UL approved to be used with the following NCA Models: FD, FD-SL, FD-N, FD-USL, FD-MB-3V, FD-MB-AF, FD-3V-SB, FDD, FDD-SL, FDD-MB-3V, and FDD-MB- & General Notes:These installation instructions apply to fire Dampers of the stat-ic, dynamic, curtain-style, single and multi-blade types mounted in the plane of a UL* approved fire partition. For dampers needed to be installed outside the plane of a UL approved wall or floor, refer to the Out of Wall fire and fire /Smoke DAMPER IOM.

All wiring shall be done in accordance with the latest edition of the National Electrical Code ANSI/NFPA-70, any local ... The opening in the fire-rated partition using the 2 angle method shall be 1/8” (3mm) per linear foot (305mm) of height and width of the sleeved assembly larger, up to a maximum of 1 ½” (38mm) and a minimum of ¼ ...

Loading..

Tags:

  Trade, Fire, Wiring

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of FIRE DAMPER INSTALLATION, OPERATION & MAINTENANCE ...

Related search queries