WBSETCL / TECH SPEC / Page 1 of 16 Fire Protection & Fire Fighting System Fire Protection & Fire Fighting System March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007 SGC113474; Website: WBSETCL / TECH SPEC / Page 2 of 16 Fire Protection & Fire Fighting System TECHNICAL SPECIFICATION FOR FIRE Protection AND FIRE Fighting System 1. SCOPE : This specification covers design, engineering, supply, delivery, erection, testing and commissioning of fire Protection and firefighting System for equipment, pump house, Control Room Buildings, Diesel Generator room etc.
WBSETCL / TECH SPEC / Rev.-1 Page 5 of 16 Fire Protection & Fire Fighting System 3. 52 KV Bushing : 630 mm 4. 36 KV Bushing : 320 mm. 5.05 Minimum water pressure available at the farthest and /or highest projector on the equipment protected shall be 3.5 kg/cm 2 However water pressure available at any projector shall not exceed 5.00 kg.cm 2 (g).