Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- F ( C) off the cooling coil at set point or below. Also, the coil delta T exceeds design, even at part load. 2. Q: What is delta T and why is it important? A: Delta T is the difference between the water return and supply temperature through a heating or cooling coil. All HVAC hydronics systems have a design delta T; however, this objective is rarely achieved at part load. Delta T is the single most effective indicator of system performance. The higher delta T, the less flow required to serve the load. 3. How fast will the leaving air temperature change when the coil flow rate varies? A: Typically, it changes a lot faster than a conventional valve can respond to.
Doc FCI-1054, Rev C; Page 2 of 7 PO Box 848 Woodinville, WA 98072 P: 425.483.1297 F: 425.486.5672 www.flowcontrol.com 8. Q: If delta T performance is poor, why can’t a facility simply reduce the pump speed to raise it? A: The system is asking for the flow it requires. Reducing the flow …
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Thermostats • High Flow Thermostats Thermostat, Thermostat, Coolant Flow Radiator And Engine Block, Single Temperature High Volume Output Thermostat, Service manual 12vdc wall thermostat, HIGH STATIC PRESSURE, DUCT TYPE PACKAGED, HIGH STATIC PRESSURE, DUCT TYPE PACKAGED AIR-CONDITIONER, Codes, High, Evocyl