GENERAL: DESIGN GUIDELINES

CONSULTANT PROCEDURES & DESIGN GUIDELINES UNIVERSITY OF MISSOURI. 337119 electrical Underground Ducts GENERAL: The scope of this document is to provide instruction for installation and testing of electric power duct banks. DESIGN GUIDELINES : 1. Materials Conduit Underground concrete encased electric conduit duct banks shall consist of Type DB-60 polyvinyl chloride (PVC) conduit rated for 90 C cable and meeting NEMA Standard TC-6 and ASTM F-512 for underground applications. The standard conduit sizes shall be 2 , 3 , 4 , and 5 for all conduits. Conduits shall have long rigid steel metallic sweep elbows, 48 minimum radius for horizontal bends and 36 radius for vertical bends.

337119 Electrical Underground Ducts 2010.01 Revised 9/23/2009 Page 4 of 4 337119 2.3.2. Seal the ends of all conduits at manhole penetrations. Seal water tight with plastic plugs with wick for drainage. Conduit pull string shall penetrate through seal.