Transcription of Generator Specifications - Yemen Mobile
{{id}} {{{paragraph}}}
1 Generator Specifications 1-General This specification covers Diesel Engine driven electric generating alternators, 380/220 Vac 10% ,3ph,4 wires ,50HZ ,1500 rpm , continuous out put rating 15kVA, and PF at altitude 2200m ASL and 40C , weather proof canopy outdoor unit. To supply the telecommunication services as an automatic units. It shall feed BTS stations through electronic thyristor based rectifiers regulated. In addition, they shall feed single phase and three phase air conditioners, single phase lights, fans etc. The tenderer shall provide evidence that similar equipment has been supplied and given satisfactory service.
3 with shutdown protection against high cylinder temperature, low lubricating oil pressure, coolant temperature, belt failure, or any other fault.