HCI 434F/444F - Technical Data Sheet - raad-eng.com

HCI 434F/444F - Technical Data SheetHCI434F/444 FSPECIFICATIONS & OPTIONSSTANDARDSN ewage Stamford industrial generators meet therequirements of BS EN 60034 and the relevant sectionof other international standards such as BS5000, VDE0530, NEMA MG1-32, IEC34, CSA , standards and certifications can be considered REGULATORSSX440 AVR - STANDARDWith this self-excited system the main stator providespower via the Automatic Voltage Regulator (AVR) to theexciter stator. The high efficiency semi-conductors ofthe AVR ensure positive build-up from initial low levelsof residual exciter rotor output is fed to the main rotor througha three-phase full-wave bridge rectifier. The rectifier isprotected by a surge suppressor against surgescaused, for example, by short circuit or SX440 will support a range of electronicaccessories, including a 'droop' Current Transformer(CT) to permit parallel operation with other 3-phase sensing is required with the self-excitedsystem, the SX421 AVR must be AVRThis AVR also operates in a self-excited system.

control system separately excited by p.m.g. a.v.r. mx321 mx341 voltage regulation ± 0.5 % ± 1.0 % with 4% engine governing sustained short circuit