HVAC Variable Refrigerant Flow Systems - seedengr.com

HVAC Variable Refrigerant Flow Systems Course No: M03-014 Credit: 3 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 Variable Refrigerant Flow (VRF) Systems Variable Refrigerant flow (VRF) is an air-condition system configuration where there is one outdoor condensing unit and multiple indoor units. The term Variable Refrigerant flow refers to the ability of the system to control the amount of Refrigerant flowing to the multiple evaporators (indoor units), enabling the use of many evaporators of differing capacities and configurations connected to a single condensing unit. The arrangement provides an individualized comfort control, and simultaneous heating and cooling in different zones.

The modern VRF technology uses an inverter-driven scroll compressor and permits as many as 48 or more indoor units to operate from one outdoor unit (varies from ... VRF heat pump systems permit heating or cooling in all of the indoor units but NOT simultaneous heating and cooling. When the indoor units are in the cooling mode, they