IEC 61508 Assessment - Emerson

Exida ROS 13-01-010 R002 V2R3 3051 IEC 61508 T-034 V4R5 Page 1 of 21 IEC 61508 Functional Safety Assessment Project: Emerson s Rosemount 3051 Pressure Transmitter with 4-20mA HART Device Label SW Company: Rosemount Inc. Shakopee, MN USA Contract No.: Q15-10-010 Report No.: ROS 13/01-010 R002 Version V2, Revision R3, October 14, 2016 Ted Stewart exida ROS 13-01-010 R002 V2R3 3051 IEC 61508 T-034 V4R5 Page 2 of 21 Management Summary This report summarizes the results of the functional safety Assessment according to IEC 61508 carried out on the: Emerson s Rosemount 3051 Pressure Transmitter with 4-20mA HART: Differential and Gage Coplanar Emerson s Rosemount 3051 Pressure Transmitter with 4-20mA HART: Coplanar Absolute, In-Line Gage and Absolute Emerson s Rosemount 3051 Level Transmitter with 4-20mA HART Emerson s Rosemount 3051 Flowmeter with 4-20mA HART The functional safety Assessment performed by exida consisted of the following activities: - exida assessed the development process used by Rosemount Inc.

© exida ROS 13-01-010 R002 V2R3 3051 IEC 61508 Assessment.docx T-034 V4R5 www.exida.com Page 3 of 21 Table of Contents Management Summary ..... 2