PNNL-18898 Prepared for the Department of Energy under Contract DE-AC05-76RL01830 Infiltration Modeling Guidelines for Commercial Building Energy Analysis K Gowri D Winiarski R Jarnagin September 2009 ii iii Executive Summary This report presents a methodology for Modeling air Infiltration in EnergyPlus to account for envelope air barrier characteristics. Based on a review of various Infiltration Modeling options available in EnergyPlus and sensitivity analysis, the linear wind velocity coefficient based on DOE-2 Infiltration model is recommended. The methodology described in this report can be used to calculate the EnergyPlus Infiltration input for any given Building level Infiltration rate specified at known pressure difference.
is the local wind pressure coefficient at the point of impingement. Studies of the variation in the local wind pressure coefficient have been made [6], however, integrating the product of the local wind pressure coefficient and the stagnation pressure across surfaces in real buildings is difficult.