LAB VENTILATIONDESIGN By: John C. Palasz, PE, HFDP Primera Lab VENTILATION Systems 1 Table of Contents SECTION I INTRODUCTION .. 2 SECTION II PROTECTING PEOPLE (AND EXPERIMENTS) .. 3 SECTION III UNDER PRESSURE .. 4 SECTION IV room CONSTRUCTION / room LAYOUT .. 5 SECTION V VERIFYING SYSTEM OPERATION .. 6 SECTION VI LAB VENTILATION SYSTEM OPTIONS .. 6 SECTION VII LAB SPACE OR CLASSROOM SPACE? .. 9 SECTION VIII CONCLUSION .. 11 Primera Lab VENTILATION Systems 2 I. Introduction If you are a Facilities Director at an elementary school, high school, or university and have been tasked with converting a standard classroom to a chemistry lab space, how do you decide what type of VENTILATION system to use?
• In the lab mode, return air isolation dampers close, the dampers and exhaust fans are engaged to a specific airflow and all of the room air is exhausted. During the lab mode, the system can be constant volume or variable volume. This allows these rooms to be safe during lab mode while saving energy during lecture mode.