LP GAS INDIVIDUAL INSTALLATION CHECK LIST …

MARCH 2008 Page 1 of 2ckSummaryCode , Liquid / Vapor In or OutMay use Backflow CHECK Valve ( ) if flow into container only ___First Stage / High Pressure Reg. direct to container vapor spaceNFPA 58 or high-pressure regulators shall be directly attached or attached by flexible connectors to the vapor service valve of a container, or to a vaporizer outlet, or to interconnecting piping of manifolded containers or painted to protect from corrosionNFPA 58 Gas Piping shall be protected against corrosion (Rust). Paint or coat not used for groundNFPA 58 piping shall not be used as a grounding damaged tubing or pipingNFPA 54(06) Gas Piping Shall be replaced___Separation Distances___Point of TransferNFPA for container relief to Building openingsNFPA between containers

NFPA 58 6.8.1.1: First-stage or high-pressure regulators shall be directly attached or attached by flexible connectors to the vapor service valve of a container, or to a