PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: barber

Material Selection for Gaseous Oxygen Service

P O B o x 3 11 5 4 S t . L o u i s, M O 6 3 1 3 1 - 0 1 5 4 P h o n e : ( 3 1 4 ) 9 6 6 - 8 9 1 9 ~ E m a i l : w m h u i t t @ a o l . c o m 1 Material Selection for Gaseous Oxygen Service by William M. Huitt (From a letter dated March 7, 2001 in response to a project s need to select tubing Material for Oxygen Service .) In selecting a pipe or tubing Material for Gaseous Oxygen Service there are four basic criteria: % Oxygen in the gas, pressure, temperature and velocity. As you can see by Fig. 1, if the system operates below 200 psig at 200 F then carbon steel or stainless steel would be suitable Material at almost any velocity. However, above those markers velocity becomes an issue and the Material Selection narrows. Figure 1 Maximum velocity versus internal pressure for steel pipelines ( mole% or higher Oxygen ) (Griffith and Wallis, Journal of Heat Transfer, August 1961) If a system is operating in a range above the curve in Fig.

G-4.1 – Cleaning Equipment for Oxygen Service G-4.4 – Industrial Practices for Gaseous Oxygen Transmission & Distribution Piping Systems O2-DIR – 2000 Directory of Cleaning Agents for Oxygen Service NFPA: 53M – Fire Hazards in …

Tags:

  Services, Equipment, Cleaning, Oxygen, For oxygen service, Oxygen service, Cleaning equipment for oxygen service

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of Material Selection for Gaseous Oxygen Service

Related search queries