Mechanical Joint InstallationMechanical Joint AssemblyFrom AWWA C600-101. Clean the socket and the plain end. Lubrication and additional cleaning should be provided by brushing both the gasket and plain end with soapy water or an approved pipe lubricant meeting the requirements of ANSI/AWWA c111 just prior to slipping the gasket onto the plain end for Joint Assembly . Place the gland on the plain end with the lip extension toward the plain end, followed by the gasket with the narrow edge of the gasket toward the plain end [The gasket provided may have been the EBAA-Seal Improved Mechanical Joint Gasket.]
Title: Standard Mechanical Joint Installation Instructions and Dimensions Author: Rick Rackow Subject: Provides installation instructions for standard Mechcanical Joints (MJ) per AWWA C600 and MJ Dimension and Specifications per ANSI/AWWA A21.11/C111 and A21.53/C153