MINIMUM REQUIREMENTS FOR THE DESIGN AND …

UG-1: GeneralGreenbook038193 Page 1 of 22 Rev. #14: 12-17-20 Electric Distribution038193 Function:Asset Type:Issued by:Date:12-17-20 Rev. #14: This document replaces PG&E Document 038193, Rev. #13 For a description of the changes, see Page REQUIREMENTS FOR THE DESIGN AND installation OFELECTRIC CONDUIT, INSULATED CABLE, AND FACILITIESP repared by: ABB1 DESIGN and ConstructionLisseth Villareal (LDV2)Purpose and ScopeThis document describes the MINIMUM REQUIREMENTS for the DESIGN and installation of electric conduits and pullinginsulated cables. This document also provides REQUIREMENTS of what facilities are allowed within the same Information1. A MINIMUM of 24 inches of cover for secondary (0 750 V) electric service, or 36 inches MINIMUM cover forprimary (over 750 V) is required.

MINIMUM REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF ELECTRIC CONDUIT, INSULATED CABLE, AND FACILITIES Prepared by: ABB1 Design and Construction Lisseth Villareal (LDV2) ... For secondary, services, and 200-Amp primary applications, the conduit run must not exceed 600 feet if there is a