Multi V IV and 5 Control System Install TipsThe following pages present an overview of Multi V Variable Refrigerant Flow (VRF) Control installation concepts, and are intended to supplement the technical and installation information provided with each product and through The review of basic installation and configuration information should provide helpful tips to make equipment Control installation guide is NOT intended to be a replacement for LG installation manuals, nor is it intended to cover ALL the possible options for Control of, or related to, VRF systems.
Identifier 0-F Second character is the Hex Member Identifier 0-F Central Controller Addressing D If the Multi V system includes a Central Controller / BMS Gateway, the installer must manually set (through the remote controller) each indoor unit with a two-character hexadecimal address: 0-9 and A-F ( but do not use Address “00”).