Non-Dwelling 13

ObjectivesAfter studying this unit, the student will:IntroductionUnit 13 contains a Non-Dwelling load calculation form, along with a detailed explanation of each calculations are covered in Unit 8 (one-family) and Unit 11 (multi-family) of this text. Unlikedwelling unit load calculations, receptacle outlets are counted. Receptacle outlets (if known) and fixedmultioutlet assemblies (if any) are entered into the calculation, and if the load is great enough, a demandfactor is applied. As with dwelling-unit load calculations, general lighting is computed using outsidedimensions. Other items, such as a sign outlet (where required) and show window(s) (if present) are partof the Non-Dwelling load calculation.

long as they will never be energized simultaneously (such as certain portions of heating and A/C systems). 12 Calculate fixed electric space heating loads at 100% of the total connected load. 220-15 13 Motor Loads 220-4(a), 430-24, 430-25, 430-26, and Article 440 Motor-driven air-conditioning and refrigeration equipment is found in Article 440. 13