Aquarius Technologies Pty. - 2002 AT_TB_018 Rev 3 Page 1 of 4 ORP Millivolts -The Sensor for Measurement of DisinfectionOxidising biocides such as gas or liquid Chlo-rine, Bromine and Ozone have been used for manyyears in potable water and swimming pools for recent years both liquid bromine for-mulations and BCDMH bromine release biocides haveproved to be very effective in control of bacterial lev-els in cooling water systems and in swimming is a very strong oxidising agent and itsuse in both cooling water systems and swimming poolsis gaining - oxidation reduction potential sensors,when coupled with differential inputs, high gain ampli-fiers and ground reference probes and microproc-essor control circuitry, can provide for automatic con-trol with dosage proportional to the disinfection sensors can also provide for both highand low alarm signals, plus, via a computer, and allthe data can be logged, to provide a hard copy recordof the ORP millivolt levels maintained and verificationof the levels

© Aquarius Technologies Pty. Ltd. March - 2002 © AT_TB_018 Rev 3 Page 2 of 4 The chemistry of chlorine solutions in water has reactions as follows :-