Parameter Settings for PowerFlex Drives Using Sine-wave ...

filter and can cause an F12 “HW OverCurrent” fault. P043 [Flux Up Mode] Set P043 to 0 “Manual” to accommodate motor control because it looks less like an equivalent motor circuit to the drive. P044 [Flux Up Time] Flux up time is set to zero because the output load looks less like an equivalent motor circuit to the drive.