Power Factor Insulation Diagnosis - University of Minnesota

A transformer core with residual magnetism can cause erroneous readings in excitation current measurements. IEEE C57.152 section 7.211.1 states that “The transformer core may have residual magnetism present as a result of being disconnected from the power line or, as is frequently the case, as a

Tags:

  Power, Factors, Core, Diagnosis, Insulation, Transformers, Power factor insulation diagnosis, Transformer core