PRC-004-3 — Protection System Misoperation Identification ...

PRC-004-6 Protection System Misoperation Identification and Correction Page 1 of 32 A. Introduction 1. Title: Protection System Misoperation Identification and Correction 2. Number: PRC-004-6 3. Purpose: Identify and correct the causes of Misoperations of Protection Systems for Bulk Electric System (BES) Elements. 4. Applicability: Functional Entities: Transmission Owner Generator Owner Distribution Provider Facilities: Protection Systems for BES Elements, with the following exclusions: Non-protective functions that are embedded within a Protection System .

PRC-004-6 — Protection System Misoperation Identification and Correction . Page 3 of 32 . 2.2 . For a BES interrupting device operation by a Protection System component intended to operate as backup protection for a condition on another entity’s BES Element, notification of the operation shall be provided to the other Protection