PRC-025-2 – Generator Relay Loadability

PRC-025-2 Generator Relay Loadability Page 1 of 114 A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-2 3. Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping of generators during a system disturbance for conditions that do not pose a risk of damage to the associated equipment. 4. Applicability: Functional Entities: Generator Owner that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities. Transmission Owner that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities. Distribution Provider that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities.

removal of dynamic Reactive Power exacerbates the severity of the voltage disturbance , and as a result changes the character of the system disturbance. In addition, the loss of Real Power could initiate or exacerbate a frequency disturbance. 7. Standard Only Definition: None. B. Requirements and Measures . R1.