PRC-025-2 Generator Relay Loadability Page 1 of 114 A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-2 3. Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping of generators during a system disturbance for conditions that do not pose a risk of damage to the associated equipment. 4. Applicability: Functional Entities: Generator Owner that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities. Transmission Owner that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities. Distribution Provider that applies load-responsive protective relays1 at the terminals of the Elements listed in , Facilities.
NERC System Protection and Control Subcommittee, “Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition.” (Date of Publication: March 2016) IEEE C37.102-2006, “IEEE Guide for AC Generator Protection.” (Date of Publication: 2006)