Presented by - Storm Technologies, Inc.

Presented by:Stephen K. StormStorm Technologies, Inc. (USA)John GuffreParagon AirheaterTechnologies (USA)June 8-10, 2010, Amsterdam, HollandIntroduction TheAirheateraccountsfor~10%ofaunit FD Fans ID Fans Pulverizers BurnersThe Airheater impacts the efficiency of most plant equipment Precipitators Bag houses Boiler Operation Environmental Equipment (SCR, FGD)Evaluating Air Heater Performance Airheaterleakagecanoccurfromdifferentpat hs. Path1:Normalairflowpath Path2:Normalgasflowpath PathA:AmbientFDfanleakingdirectlytotheAP HGasOutlet PathB:Pre-heatedFDfanairflowshortcircuit ingtheAPH PathC:AmbientFDfanairleakingaroundairhea ter.

Introduction • The Air heater accounts for ~10% of a unit’sthermal efficiency and is a critical component of combustion system. Air heater leakage has a major