Propylene Glycol - Refrigerants

Distributed By: National Refrigerants , Roosevelt Boulevard Philadelphia, PA fax: web: e-mail: GlycolContains DOWFROST heat transfer fluidFreeze protection is required if a system is going to be actively pumping fluid at the lowest ambient temperature and/or where there is no room in the system for expansion to accommodate an ice/slush formation. To obtain adequate freeze protection, the Glycol solution must maintain a freezing point at least 5 F lower than ambient FREEZE PROTECTIONFOR BURST PROTECTIONTEMPV olume %TEMPV olume % FPG35PG40PG45PG70PG96 FPG35PG40PG45PG70PG962049433825182033292 6161210807062402910554843272009986774936 06658513324-10905842-107767603828-209863 46-208272644130-306950-309179704533-4074 54-409684754835-507857-509684754835-6082 60-609684754835 Table 1: Many industrial and commercial water systems are required to operate at temperatures below the freezing point of water.

Burst protection is required if the system will sit dormant at temperatures below the freezing point of the fluid and there is adequate space to accommodate

Tags:

  Glycol, Propylene, Propylene glycol, Freezing