Protection Basics Copyright SEL 2013. Protection Review Fault types Electrical equipment damage Time versus current plot Protection requirements Protection system elements Power System Faults Short circuits Contacts with ground Isolated neutral systems High-impedance grounded systems Open phases Typical Short-Circuit-Type Distribution Single-phase-to-ground 70 80%. Phase-to-phase-to-ground 10 17%. Phase-to-phase 8 10%. Three-phase 2 3%. Faults in Electrical Systems Produce Current Increments a Distribution b Substation c I.
Nov 18, 2019 · Understand Basic Protection Principles • Overcurrent (50, 51, 50N, 51N) • Directional overcurrent (67, 67N) • Distance (21, 21N) • Differential (87) Overcurrent Relays Protect Radial Lines = LOAD ++ Source Line LOAD E I Z ZZ = FAULT + Source Line E I Z m•Z I