Refrigerant Piping HandbookRefrigerant Piping DenisonAcknowledgementsSuvarefrigerants DedicationThe author wishes to acknowledge the contribution of various friends, co-workers and former colleagues. Gino DiFebo, Nick Reggi, Wesley Taylor and Laurence White enriched the pages of this work with their perspectives and knowledge. Itwas their participation, discussions, review and comments thatmade this publication the advancement of the profession and its of ContentsEngineering OnePiping ThreePiping FourExpansion / Contraction ..Section FiveBest SixQuick Pick SevenHFC Quick Pick Tables ..Section EightHCFC Quick Pick Tables.
Good refrigeration piping design requires that the refrigeration lines be pitched in the direction of flow at approximately 1/2 inch per 10 feet or 1 inch per 20 feet. Refrigerant velocities in vertical lines should be at least 1500 ft/min to ensure good oil return;