1. REQUIREMENTS FOR COMPONENTS used IN INDUSTRIAL. CONTROL PANELS. February 4, 2019. This document is intended to be used to determine the REQUIREMENTS for COMPONENTS when used in industrial control panels. This document replaces what was Supplement SA in the Second Edition of UL 508A, and subsequently Appendix C in the Third Edition of UL 508A. It supersedes the previous version of this document dated June 20, 2018. References in this document to sections or paragraphs in UL 508A are understood to be to the third edition of the standard with revisions dated July 3, 2018. This document will be updated on an as-needed basis as changes occur in the use of COMPONENTS in panels. The current version will be stored on UL's Industrial Control Panel website.
Section 12 - Insulating Barriers meeting component selection requirements of 12.2 12.2(a)(1) Generic materials - - Type and minimum thickness as specified in Table 12.1, dimensions of barrier shall also comply with 12.1 12.2(a)(2) Recognized Sleeving UL 1441 UZFT2 90°C (194°F) minimum and for voltage involved, as noted on Recognition