Transcription of Safety Function: GuardLogix Controller Connected to a ...
{{id}} {{{paragraph}}}
Application TechniqueSafety Function: GuardLogix Controller Connected to a Series of Dual-channel E-stop ButtonsProducts: Compact GuardLogix Controller , POINT Guard I/O Module, Dual-channel E-stop ButtonSafety Rating: CAT. 3, PLd to ISO 13849-1: 2008To picPa geImportant User Information2 General Safety Information3 Introduction3 Safety Function Realization: Risk Assessment4 Emergency Stop Safety Function4 Safety Function Requirements4 Functional Safety Description4 Bill of Material5 Setup and Wiring5 Configuration7 Calculation of the Performance Level15 Verification and Validation Plan17 Additional Resources192 Rockwell Automation Publication Safety -AT080C-EN-P - May 2016 Safety Function: GuardLogix Controller Connected to a Series of Dual-channel E-stop ButtonsImportant User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product.
Safety Function: GuardLogix Controller Connected to a Series of Dual-channel E-stop Buttons Safety Function Realization: Risk Assessment The required performance level is the result of a risk assessment and refers to the amount of the risk reduction to be carried out by the safety-related parts of the control system.
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document: